IR-P Infrared Optical Sensor
FOR CLEAR FLUIDS ONLY
Installation and Technical Data Guide
AW Flow Meters 8809 Industrial Drive, Franksville, WI Phone: (262) 884-9800 Fax: (262) 884-9810
Email: [email protected] www.awflowmeters.com
Rev 09/05
IR-P
A Sinking Output Circuit
~40 Ohm
SUPPLY
OUTPUT
GROUND
Analog
Switch
User may need to add external components to interface to
displays or other instruments
User must limit output voltage to Supply -1V
Max current sinking capability: 50mA
Supply Voltage: +10 to 26 Volt DC
Supply Current: 20 mA ± 0.10
Duty Signal: 50% ± 15%
Minimum Signal: 0.5 Hz
Frequency Output: TBD
Driving Capacity: 50 mA Max resistive load
Output Impedance: ~ 40 Ohm - analog switch and self-resetting fuse
Temperature Range: -40° F to 185° F (-40° C to 85° C)
Technical Dat
a:
Signal output square wave:
V
high
= Supply -1V @ no output load
V
low
= 0.1V
Max sourced output voltage: Supply -0.5V
Max current sourcing capabilities: 50mA
~40 Ohm
SUPPLY
OUTPUT
GROUND
Analog
Switch
IR-PB Sourcing Output Circuit